1.5 Parameter Overview
Parameter Overwiev
0-** Operation/Display
0-0* Basic Settings
0-03 Regional Settings
*[0] International
[1] US
0-04 Oper. State at Power-up
(Hand)
[0] Resume
*[1] Forced stop, ref=old
[2] Forced stop, ref=0
0-1* Set-up Handling
0-10 Active Set-up
*[1] Setup 1
[2] Setup 2
[9] Multi Setup
0-11 Edit Set-up
*[1] Setup 1
[2] Setup 2
[9] Active Setup
0-12 Link Setups
[0] Not Linked
*[20] Linked
0-31 Custom Readout Min Scale
0.00 9999.00 * 0.00
0-32 Custom Readout Max Scale
0.00 9999.00 * 100.0
0-4* Keypad
0-40 [Hand on] Key on
[0] Disabled
*[1] Enabled
0-41 [Off / Reset] Key on
[0] Disable All
*[1] Enable All
[2] Enable Reset Only
0-42 [Auto on] Key on
[0] Disabled
*[1] Enabled
0-5* Copy/Save
0-50 Copy
*[0] No copy
[1] All to
[2] All from
[3] Size indep. from
0-51 Set-up Copy
*[0] No copy
[1] Copy from setup 1
[2] Copy from setup 2
[9] Copy from Factory setup
0-6* Password
0-60 (Main) Menu Password
0-999 *0
0-61 Access to Main/Quick Menu
w/o Password
*[0] Full access
[1] LCP:Read Only
[2] LCP:No Access
1-** Load/Motor
1-0* General Settings
1-00 Configuration Mode
*[0] Speed open loop
[3] Process
1-01 Motor Control Principle
[0] U/f
*[1] VVC+
1-03 Torque Characteristics
*[0] Constant torque
[2] Automatic Energy Optim.
1-05 Local Mode Configuration
[0] Speed Open Loop
*[2] As config in par. 1-00 1-2*
Motor Data
1-20 Motor Power [kW] [HP]
[1] 0.09 kW/0.12 HP
[2] 0.12 kW/0.16 HP
[3] 0.18 kW/0.25 HP
[4] 0.25 kW/0.33 HP
[5] 0.37 kW/0.50 HP
[6] 0.55 kW/0.75 HP
[7] 0.75 kW/1.00 HP
[8] 1.10 kW/1.50 HP
[9] 1.50 kW/2.00 HP
[10] 2.20 kW/3.00 HP
[11] 3.00 kW/4.00 HP
[12] 3.70 kW/5.00 HP
[13] 4.00 kW/5.40 HP
[14] 5.50 kW/7.50 HP
[15] 7.50 kW/10.00 HP
[16] 11.00 kW/15.00 HP
[17] 15.00 kW/20.00 HP
[18] 18.50 kW/25.00 HP
[19] 22.00 kW/29.50 HP
[20] 30.00 kW/40.00 HP
1-22 Motor Voltage
50-999 V *230 -400 V
1-23 Motor Frequency
20-400 Hz *50 Hz
1-24 Motor Current
0.01-100.00 A *Motortype dep.
1-25 Motor Nominal Speed
100-9999 rpm *Motortype dep.
1-29 Automatic Motor Tuning
(AMT)
*[0] Off
[2] Enable AMT
1-3* Adv. Motor Data
1-30 Stator Resistance (Rs)
[Ohm] * Dep. on motor data
1-33 Stator Leakage Reactance (X1)
[Ohm] * Dep. on motor data
1-35 Main Reactance (Xh)
[Ohm] * Dep. on motor data
1-5* Load Indep. Setting
1-50 Motor Magnetisation at 0
Speed
0-300% *100%
1-52 Min Speed Norm. Magnet. [Hz]
0.0-10.0 Hz *0.0Hz
1-55 U/f Characteristic - U
0-999.9 V
1-56 U/f Characteristic - F
0-400 Hz
1-6* Load Depen. Setting
1-60 Low Speed Load Compen-
sation
0-199% *100%
1-61 High Speed Load Compen-
sation
0-199% *100%
1-62 Slip Compensation
-400-399% *100%
1-63 Slip Compensation Time
Constant
0.05-5.00 s *0.10 s
1-7* Start Adjustments
1-71 Start Delay
0.0-10.0 s *0.0 s
1-72 Start Function
[0] DC hold/delay time
[1] DC brake/delay time
*[2] Coast/delay time
1-73 Flying Start
*[0] Disabled
[1] Enabled
1-8* Stop Adjustments
1-80 Function at Stop
*[0] Coast
[1] DC hold
1-82 Min Speed for Funct. at Stop
[Hz]
0.0-20.0 Hz *0.0 Hz
1-9*Motor Temperature
1-90 Motor Thermal Protection
*[0] No protection
[1] Termistor warning
[2] Thermistor trip
[3] Etr warning
[4] Etr trip
1-93 Thermistor Resource
*[0] None
[1] Analog input 53
[6] Digital input 29
2-** Brakes
2-0*DC-Brake
2-00 DC Hold Current
0-150% *50%
2-01 DC Brake Current
0-150% *50%
2-02 DC Braking Time
0.0-60.0 s *10.0s
2-04 DC Brake Cut In Speed
0.0-400.0 Hz *0.0Hz
2-1* Brake Energy Funct.
2-10 Brake Function
*[0] Off
[1] Resistor brake
[2] AC brake
2-11 Brake Resistor (ohm)
5 -5000 *5
2-16 AC Brake, Max current
0-150% *100%
2-17 Over-voltage Control
*[0] Disabled
[1] Enabled (not at stop)
[2] Enabled
2-2* Mechanical Brake
2-20 Release Brake Current
0.00-100.0 A *0.00 A
2-22 Activate Brake Speed [Hz]
0.0-400.0 Hz *0.0 Hz
3-** Reference / Ramps
3-0* Reference Limits
3-00 Reference Range
*[0] Min - Max
[1] -Max - +Max
3-02 Minimum Reference
-4999-4999 *0.000
3-03 Maximum Reference
-4999-4999 *50.00
3-1* References
3-10 Preset Reference
-100.0-100.0% *0.00%
3-11 Jog Speed [Hz]
0.0-400.0 Hz *5.0 Hz
3-12 Catch up/slow Down Value
0.00 - 100.0% * 0.00%
3-14 Preset Relative Reference
-100.0-100.0% *0.00% 3-15
Reference Resource 1
[0] No function
*[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] Potentiometer
3-16 Reference Resource 2
[0] No function
[1] Analog Input 53
*[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] Potentiometer
3-17 Reference Resource 3
[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
*[11] Local bus ref
[21] Potentiometer
3-18 Relative Scaling Ref. Resource
*[0] No function
[1] Analog Input 53
[2] Analog input 60
[8] Pulse input 33
[11] Local bus ref
[21] Potentiometer
3-4* Ramp 1
3-40 Ramp 1 Type
*[0] Linear
[2] Sine2 ramp
3-41 Ramp 1 Ramp up Time
0.05-3600 s *3.00 s (10.00 s
1)
)
3-42 Ramp 1 Ramp Down Time
0.05-3600 s *3.00s (10.00s
1)
)
3-5* Ramp 2
3-50 Ramp 2 Type
*[0] Linear
[2] Sine2 ramp
3-51 Ramp 2 Ramp up Time
0.05-3600 s *3.00 s (10.00 s
1)
)
3-52 Ramp 2 Ramp down Time
0.05-3600 s *3.00 s (10.00 s
1)
)
3-8* Other Ramps
3-80 Jog Ramp Time
0.05-3600 s *3.00 s (10.00s
1)
)
3-81 Quick Stop Ramp Time
0.05-3600 s *3.00 s (10.00s
1)
)
1)
M4 and M5 only
Table 1.8
Quick Guide
VLT
®
Micro Drive Quick Guide
10 MG02B702 - VLT
®
is a registered Danfoss trademark