Illustration 1.1 Mechanical Dimensions
Power [kW] Height [mm] Width [mm]
Depth
1)
[mm]
Max. Weight
Frame 1X200-240 V 3X200-240 V 3X380-480 V A
A (incl. decoupling
plate)
a B b C Kg
M1 0.18-0.75 0.25-0.75 0.37-0.75 150 205 140.4 70 55 148 1.1
M2 1.5 1.5 1.5-2.2 176 230 166.4 75 59 168 1.6
M3 2.2 2.2-3.7 3.0-7.5 239 294 226 90 69 194 3.0
M4 11.0-15.0 292 347.5 272.4 125 97 241 6.0
M5 18.5-22.0 335 387.5 315 165 140 248 9.5
1)
For with potentiometer, add 7.6 mm.
Table 1.4 Mechanical Dimensions
1.3.3
Electrical Installation in General
NOTE
All cabling must comply with national and local
regulations on cable cross-sections and ambient
temperature. Copper conductors required, (60-75 °C)
recommended.
Power [kW] Torque [Nm]
Frame 1x200-240 V 3x200-240 V 3x380-480 V Line Motor DC connection/Brake Control Terminals Earth Relay
M1 0.18-0.75 0.25-0.75 0.37-0.75 1.4 0.7
Spade
1)
0.15 3 0.5
M2 1.5 1.5 1.5-2.2 1.4 0.7
Spade
1)
0.15 3 0.5
M3 2.2 2.2-3.7 3.0-7.5 1.4 0.7
Spade
1)
0.15 3 0.5
M4 11.0-15.0 1.3 1.3 1.3 0.15 3 0.5
M5 18.5-22.0 1.3 1.3 1.3 0.15 3 0.5
1)
Spade connectors (6.3 mm Faston plugs)
Table 1.5 Tightening of Terminals