VLT
®
FCD Series
Programming, FCD
300
515-544 Data readout
Value:
Par.
no.
Description Display text Unit Update
interval
515 Res. reference (REFERENCE %) %
516 Res. reference [Unit] (REFERENCE [UNIT]) Hz, rpm
517 Feedback [Unit] (FEEDBACK [UNIT]) Par. 416
518 Frequency (FREQUENCY) Hz
519 Frequency x scale (FREQUENCY X SCALE) Hz
520 Motor current (MOTOR CURRENT) Amp
521 Torque (TORQUE) %
522 Power[kW] (POWER (KW)) kW
523 Power[HP] (POWER (HP)) HP
524 Motor voltage (MOTOR VOLTAGE) V
525 DC-link voltage (DC LINK VOLTAGE) V
526 Thermal load motor (MOTOR THERMAL) %
527 Thermal load inverter (INV. THERMAL) %
528 Digital input (DIGITAL INPUT) Bin
529 Term.53, analogue input (ANALOG INPUT 53) V
531 Term.60, analogue input (ANALOG INPUT 60) mA
532 Term. 33, pulse input (PULSE INPUT 33) Hz
533 External ref. (EXT. REF.%) %
534 Status word, Hex (STATUS WORD) Hex
537 Inverter temperature (INVERTER TEMP.) °C
538 Alarm word (ALARM WORD) Hex
539 Control word (CONTROL WORD) Hex
540 Warning word (WARN. WORD) Hex
541 Extended status word (EXT. STATUS WORD) Hex
544 Pulse count (PULSE COUNT)
545 Term. 29, pulse input (PULSE INPUT 29) Hz
Function:
These parameters can be read out via the serial
communication port and the LCP display. See also
parameters 009-012 D isplay readout.
NB!:
Parameters 515-541 can only be read out
via the serial communication port.
Description of choice:
Resulting reference %, parameter 515:
Gives the resulting reference as a percentage in the
range from Minimum reference, Ref
MIN
to Maximum
reference, Ref
MAX
. See also Dealing with references.
Resulting reference [unit], parameter 516:
Gives the resulting reference in Hz in Open loop
(parameter 100). In a closed loop the reference unit
is selected in parameter 416 Process units.
Feedback [unit], parameter 517:
Gives the resulting feedback value with the
unit/scaling selected in parameters 414, 415 and
416. See also dealing with feedback.
Frequency [Hz], parameter 518:
Gives the output frequency from the
frequency converter.
Frequency x sca ling [-], parameter 519:
corresponds to the present output frequency f
M
multiplied by the factor preset in parameter 008
Display scaling of output frequency .
= factory setting. () = display text [] = value for use in communication via serial communication port
MG.04.B7.02 - VLT is a registered Danfoss trademark
93

Table of Contents

Other manuals for Danfoss VLT FCD 307

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Danfoss VLT FCD 307 and is the answer not in the manual?

Danfoss VLT FCD 307 Specifications

General IconGeneral
BrandDanfoss
ModelVLT FCD 307
CategoryDC Drives
LanguageEnglish

Related product manuals