Parameter Option Default Usage
6-13 Terminal 53 High Current
0–20 mA 20 mA Enter the current that corresponds
to the high reference value.
6-19 Terminal 53 mode
[0] Current
[1] Voltage
1 Select if terminal 53 is used for
current or voltage input.
30-22 Locked Rotor Detection
[0] Off
[1] On
[0] Off –
30-23 Locked Rotor Detection Time [s]
0.05–1 s 0.10 s –
Table 4.4 Set-up Wizard for Open-loop Applications
Programming
Quick Guide
MG18A622 Danfoss A/S © 08/2014 All rights reserved. 33