15-20 Historic Log: Event to 15-22 Historic Log: Time
15-30 Alarm Log: Error Code to 15-32 Alarm Log: Time
NOTICE
Parameters selected in 0-25 My Personal Menu stay
present with default factory setting.
Manual initialisation
NOTICE
When carrying out manual initialisation, serial communi-
cation, RFI filter settings and fault log settings are reset.
Removes parameters selected in 0-25 My Personal Menu.
1. Disconnect from mains and wait until the display
turns off.
2. Press
2a [Status] - [Main Menu] - [OK] at the
same time while power up for Graphical
LCP (GLCP).
2b [Menu] while power up for LCP 101,
Numerical Display.
3. Release the keys after 5 s.
4. The frequency converter is now programmed
according to default settings.
This parameter initialises all except:
15-00 Operating hours
15-03 Power Up's
15-04 Over Temp's
15-05 Over Volt's
How to Operate the Frequenc... VLT HVAC Drive FC 102 Operating Instructions
MG11F402 - Rev. 2013-12-16 79
5 5