How to reset Safe Stop on Danfoss VLT HVAC Drive FC 102?
- DDeborah GrayAug 25, 2025
If Safe Torque Off has been activated on your Danfoss DC Drives, apply 24 V DC to terminal 37, then send a reset signal.
How to reset Safe Stop on Danfoss VLT HVAC Drive FC 102?
If Safe Torque Off has been activated on your Danfoss DC Drives, apply 24 V DC to terminal 37, then send a reset signal.
What does parameter error mean on Danfoss DC Drives?
If your Danfoss DC Drives displays a parameter error, it means the parameter is out of range.
What to do if Danfoss DC Drives show an over current error?
If you are experiencing an over current error with your Danfoss DC Drives, it might be due to shock loading or quick acceleration with high-inertia loads. First, remove the power and check if the motor shaft can be turned. Also, verify that the motor size matches the frequency converter and that the motor data is correctly set in parameters 1-20 to 1-25.
How to troubleshoot earth (ground) fault in Danfoss VLT HVAC Drive FC 102?
If your Danfoss DC Drives report an earth (ground) fault, it means there is current from the output phase-to-ground. To resolve this, remove power to the frequency converter and repair the ground fault. Check for ground faults in the motor by measuring the resistance to ground of the motor cables and the motor with a megohmmeter. You may also need to reset any potential individual offset in the 3 current transducers in the frequency converter.
What to do when Danfoss VLT HVAC Drive FC 102 DC Drives show an internal fault?
When an internal fault occurs in Danfoss DC Drives, a code number is shown. To resolve this: * Cycle power. * Check that the option is properly installed. * Check for loose or missing wiring.
What to do if Danfoss DC Drives power off?
What to do if Danfoss Media Converter shows WARNING 1, 10 Volts low?
What to do if I get Alarm 68, Safe Stop on my Danfoss Controller?
How to resolve Earth Fault 2 on Danfoss VLT HVAC Drive FC 102?
Enclosure | IP20, IP21, IP55 |
---|---|
Ambient Temperature Range | -10°C to +40°C |
Storage Temperature Range | -25°C to +70°C |
Relative Humidity | 5-95% (non-condensing) |
Communication Protocols | Modbus RTU, BACnet, Profibus |
Certifications | CE, UL, cUL |
Control Principle | PWM |
Cooling Method | Forced air cooling |
Input Voltage | 200-240V, 380-480V, 525-600V |
Control Modes | sensorless vector control, closed loop vector control |