46210/46220-0998 <90-00036> PAGE 51
The CPM LONG command sets the time period for control
points that are set for extended (E) operation (switches S6-1
through S6-8). The CPM SHORT command sets the time period
for control points that are set for short (S) operation (switches
S6-1 through S6-8). See the OPTION command for more
inFormat:ion.
NOTE: When setting long or short time periods, the 46220 will use the
switch settings (S3) for extended and short operation to
determine what control points to set for long or short time
periods. Extended and short operation (see OPTION command)
must be reset before operating the control points if something
different from the switch settings is desired.
The command CPM PER sets a unique time period for momen-
tary operation of a specific control point.
Use the command CPM # SET to operate the control points.
Input Example:
>CPM 2 LONG 200
If CPM points to be operated defaulted to something other than
extended (E) operation, the CPM options must be reset, as
shown below.
>CPM 2 OPT E E E E E E E E E E E E S S S S
>CPM 2 SET 1-12
This example would set control points 17-28 (points 1-12 of
subgroup 2) for 20 seconds.
Output Response:
The output response is the same as the CPM POINT SET
command.
Input Example:
>CPM 2 PER 16 100
>CPM 2 SET 16
PRINTER SYNTAX