3.0 Accessing the Zone Master Con guration
Only units where the Zone Master is being eld added require the following con guring steps.
Units with factory installed Zone Master do not require the following steps.
WARNING: Zone Master Activation Code
Units that are being retro tted with Zone Master ( eld installed) require an activation code.
Prior to con guring the Zone Master contact Data Aire Parts Sales and get your Activation Code
for every unit in the zone. This will require the Controller ID located in the Information Menu
(Menu F).
To enable the Zone Master mode, enter the Service or Factory Password.
Press the Menu button. The following screen will be displayed:
Press the Enter key. The cursor will “ ash” on the rst 0. Enter a value by pressing either the Up
or Down keys. Once a value has been entered, press the Enter key to advance to the next input
(0). The cursor will ash on the input. Enter a value by pressing the Up or Down keys. Continue
until all four inputs have the password entered (the service password is 0000, the factory pass-
word is 0002).
Press the Enter key.
The display will show the Main Menu
With the Factory Password or Service Password entered, press and hold the MENU key for ten
(10) seconds. The Zone Master Activation page will be displayed.
Security Access
Insert Service/Factory
Level password: 0000
Zone Master Control
Insert Zone Master
Access password: 0000