1.0 Introduction
The Zone Master offers unit lead/lag, rotation and a teamwork control solution for Data Aire units.
The Zone Master consists of one Master Unit and up to fteen (15) Slave Units. Unit #1 is always
assigned as the Master Unit (U1). Units #2 through #16 are slave units. Zone Master control logic
is con gured in the Master unit.
The Zone Master units are connected together in a daisy chain topology using the dap4 pLAN
communication port (see the dap4 Zone Master wiring connections on page 9).
Note: The Zone Master is optional and requires an Activation Code for each unit in the zone.
The Zone Master provides selectable logic choices as listed below:
Auto Lead/Lag Standby Rotation
Secondary Operating Schedule for Economical Control
Activate Standby Unit on Selectable Alarm
Turn Unit Off Selectable Alarm
Zone Inhibit Control Preventing Units from Con icting Operations
Standby Unit Activation on Temperature Control
1.1 Logic
1.1.1 Auto Lead/Lag Standby Rotation and Temperature Assist Logic – provides a means to au-
tomatically rotate the designation of STANDBY among a group of units that must be ON based on
programmable schedule.
The user may assign a number of units to a zone where a number units must always be ON and
others in STANDBY or OFF. ON units will have a PRIMARY designation on their status page at
the Zone Master’s display screen.
ON units will have a ONbyZM (On by Zone Master) designation at status display.
STANDBY will have a STBbyZM (Standby by Zone Master) designation.
Units that are ONbyZM but do not display the PRIMARY designation, have been brought ON by
the Zone Master because of a temperature requirement or an alarm.
OFF units will have a OFFbyZM (Off by Zone Master) designation.
The OFF mode setting will cause the blower and all cooling, heating, dehumidi cation and humidi-
cation functions to be held off regardless of the zone’s requirements. The main control display
will display the following message: OFFbyZM
The message will also be displayed in the summary page of the master unit (such as – Status:
OFFbyZM).