V130108E iBoot-G2+ Page 29
Heartbeat Commands
These commands are only available to the administrator.
get heartbeat This command displays the heartbeat settings
StatusTriggerCount
Source:NoneOK0
Frequency:10
FailCount:3
Action:None
Outlet:Main
set heartbeat source <none | usb |
network>
This command sets the source for the heartbeat.
Either USB or Network
None
set heartbeat port <1-65535> This command sets the port for the heartbeat protocol.
The heartbeat uses UDP and can be the same port
number as DxP, which is TCP
9100
set heartbeat frequency <1-999> This command is used to set the frequency, in
seconds. How often the iBoot-G2+ expects the
heartbeat
10
set heartbeat failcount <1-999>
This command is used to set the number of
consecutive failures the heartbeat must detect before
the iBoot-G2+ considers the device to be failed.
3
set heartbeat action <none | on-latch | on-
follow | off-latch | off-follow | cycle>
This command is used to set the action that the iBoot-
G2+ will perform when the heartbeat detector triggers.
None
set heartbeat cycle <1-999> This command sets the maximum number of power
cycles when the heartbeat triggers
1
set heartbeat outlet <main | exp1 | exp2> This command sets the outlet that the heartbeat will
trigger.
Main
User Commands
These commands are only available to the administrator.
set user account <yes | no> This command sets whether or not a user account is
used. If <n> only the administrator account is active
n
set login required <yes | no> This command sets whether or not a login is required
for user level operation. A login is always required for
admin functions.
y
set password <user | admin> <old> <new>
<repeat>
This command is used to set the password of either
the user or administrator.
user
admin