MIOX AE Series Operators Manual
102-00085-E Page 34
No other display information is provided. This condition is the result of the oxidant tank high level float stuck
in the high position when it should be low. For example, the tank is full and the unit enters “STANDBY” and
displays “TANK FULL”. The tank begins draining and the high level float does not drop. The display will
state the tank is full instead of stating that the tank is draining or draining is done.
7. BAD CELL PS
No other display information is provided. This condition is the result of the 12VDC power supply not turning
on or fails to meet the minimum 10 VDC to the cell.
8. RELAY FAILURE
No other display information is provided. This condition occurs when the cell power supply solid state relay is
damaged and cannot be turned off by the controller. The system must be turned off manually with the main
breaker/on-off switch. Contact your MIOX sales agent or MIOX Corporation Customer Support for service.
External Controls
An external relay is provided and can be configured for either water boost activation or alarm. For
application-specific wiring information, contact MIOX Customer Service.