59
BARRIERS
STANDARD PROGRAMMING
1 Power Supply
Give power supply, the display shows the following symbols “ ”, “ ”, “ ” and then “----”.
* If the control panel has already been programmed and the power fails or is switched off  - once power is returned and a START com-
mand is given, the position reset procedure is performed (see “rESP” in the table “WORKING STATUS MESSAGES” on page 68.
2 Visualisation of inputs and operations-counter status
1.  Press the   key for 15 seconds;
2.  The display will show respectively:
Inputs status (check it’s correct);
   
Total operations counter (* see P064):
i.g.: 
 = 3x100* = 3000  operations performed
Maintenance operations-counter (* see P065):
i.g.:    =  5*x500  =  2500  operations  remaining 
before  the  maintenance  intervention  request  (
  = 
manoeuvres-counter disabled)
3.  Hold down the 
 key to display a cyclic 3 options, or 
release the 
 button to exit the parameter.
3 Selection type of operators    !  IMPORTANT  !
1.  Scroll down the parameters with   and   keys until you vi-
sualise P028;
2.  Access the parameter by pressing the 
 key;
3.  Acting on 
 and   keys, set:
  - d003=PASS;
  - d004=STOP;
4.  Confirm your choice by pressing the   key  (display returns 
again to P028).
4 Selection operating with or without encoder    !  IMPORTANT  !
Warning: Remember to correctly set the jumpers J5 and J9.
BB
AA
A position = operators with encoder (remind to set P029=0)
B position = operators without encoder (remind to set P029=1)
1.  Scroll down the parameters with   and   keys until you vi-
sualise P029;
2.  Access the parameter by pressing the 
 key;
3.  Acting on 
 and   keys, set:
  - d000=for operators with encoder;
  - d001=for operators without encoder;
4.  Confirm your choice by pressing the 
 key (display returns 
again to P029).