Confirm that blowers were not operated with construction dust present in the space or in the unit ducts.
Confirm that all air filters were clean and in place during airflow measurements.
Confirm that all shipping blocks were removed prior to operating the supply-air blower.
Confirm that all blower belts (if any) were properly aligned and tensioned during airflow measurements.
Confirm that all ducts, diffusers, grilles, dampers, etc., were unobstructed during all airflow measurements.
For units with the SmartSaver, economizer, or Purge options, confirm that procedures given in the
appropriate Dectron manual appendix were followed.
Confirm that all damper stops (if any) are set.
Confirm that blower voltages and currents are within tolerance per the unit nameplate.
Confirm that all blowers turn in the correct direction.
The supply-air flow was measured to be .
The outdoor-air intake flow was measured to be .
The exhaust-air flow was measured to be .
Pool 1 water flow (if any) through the unit was measured to be .
Pool 2 water flow (if any) through the unit was measured to be .
Pool 3 water flow (if any) through the unit was measured to be .
Pool 4 water flow (if any) through the unit was measured to be .
For units with water-cooled air conditioning, the cooling-water flow was measured to be .
For units with DryCooler-cooled air conditioning, the glycol flow was measured to be .
For units with hot-water or steam space heat, the space-heating capacity
was measured to be .
Confirm that all temporary jumpers have been removed.
Leave a copy of this checklist with the unit.
Dectron, Inc. March 2012
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owners Manual
T.A.B. Checklist
Data subject to change without notice.
206
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
your
initials
Date: ________________
Model No. ________________
Serial No. ________________
Ref. No. _________________
Name _________________
Tel. _________________
CFM
CFM
CFM
GPM (l/m)
GPM (l/m)
GPM (l/m)
GPM (l/m)
GPM (l/m)
GPM (l/m)
BtuH (kW)
your
initials
your
initials
your
initials
your
initials
T.A.B.
5.38

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DSV 040 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DSV 040 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DSV 040
CategoryController
LanguageEnglish

Related product manuals