Dectron, Inc. March 2012
Owner’s Manual
DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Pre-Startup Adjustments Startup
Data subject to change without notice.
213
Samples
Appearance
may vary.
DECTRON
Some units may ship with wooden spacer blocks to maintain component positions during shipping. Open the
unit access panels or doors and remove any wooden blocks.
Where wire or plastic wraps are used to hold the wooden blocks in place, remove them also. Do not leave
loose materials inside the unit.
NOTE: Do not remove any perforated-channel braces unless specifically instructed to do so.
Some units may ship with a metal brace restraining the top of the
compressor(s). Inspect the compressors and remove any top braces.
Some units may ship with compressor mounting springs compressed.
Where this is the case, loosen the bolts just enough to allow the
compressor(s) to float on the springs.
Refrigerant distributor tubes may be touching after shipment. Operating
the unit with tubes touching each other can lead to refrigerant leaks.
Inspect all the distributor tubes and gently separate them so that they do
not touch. If necessary, separate them with plastic spiral wrap, rubber
strips, silicone caulk, etc.
Carefully test all refrigerant tubes, refrigerant components, and tube joints
(including factory joints) for leaks, using a reliable electronic leak detector.
Repair all leaks as necessary.
STARTUP