A/C ON - The Air-Conditioning feature is operating.
AIR HEATING CALL - The temperature of the room is below set point minus offset minus differential.
ASCT X ON
- The minimum OFF time for compressor X has not elapsed.
AUX. AIR HEATING ON STAGE 1
- First stage auxiliary air heating is ON.
AUX. AIR HEATING ON STAGE 2
- Second stage auxiliary air heating is ON.
AUX. AIR HEATING ON STAGE 3 - Third stage auxiliary air heating is ON.
AUX. AIR HEATING ON STAGE 4
- Fourth stage auxiliary air heating is ON.
BLOWER ON
- Blower is operating.
BLOWER REMOTE SWITCH OFF
- The blower is turned off by remote manual input.
BLOWER TURNED OFF - See Startup - Enable Operation.
COMPRESSOR X EMERGENCY SWITCH OFF - The manual ON/OFF switch is OFF.
COMPRESSOR X PUMPDOWN
- Compressor X is preparing to shut down.
COMPRESSOR X TURNED OFF - See Startup - Enable Operation.
COOLING CALL -
The temperature of the room is above set point plus offset plus
differential.
DEHUMIDIFICATION CALL - The relative humidity of the room is above set point plus differential.
DEHUMIDIFICATION ON
- One or more compressors are operating.
EVAPORATOR DAMPER CLOSED - The evaporator bypass damper is closed to divert air to the evaporator.
ECONOMIZER ON - The Economizer feature is operating.
GAS BOILER ON - The gas boiler on units so equipped is operating.
LEAD LAG ON - Compressor 2 is first stage.
MANUAL RESET REQUIRED -
A fatal alarm has occurred. See Operation - Start, Stop, Reset.
MAXIMUM EXHAUST BLOWER ON - The maximum amount of room air is being exhausted.
MINIMUM EXHAUST BLOWER ON - The standby amount of room air is being exhausted.
OCCUPIED PERIOD - Time-of-day is defined as that in which people are usually present.
OIL RETURN MODE X ON
- Refrigerant is being diverted through the outdoor condenser for oil return.
PLEASE WAIT... Compressor X will auto reset - A possibly fatal alarm is being analyzed.
POOL 1 AUX ON - An auxiliary heater is heating pool 1 water.
POOL 2 AUX ON - An auxiliary heater is heating pool 2 water.
POOL 1 HEATING CALL - The temperature of pool 1 water is below set point minus differential.
POOL 2 HEATING CALL - The temperature of pool 1 water is below set point minus differential.
POOL 1 HEATING ON - Water from pool 1 is being heated.
POOL 2 HEATING ON - Water from pool 2 is being heated.
PURGE MODE ON - Room air is being exhausted to dilute superchlorination gases.
VENTILATION ON
- Cooling or dehumidification by ventilation is enabled in the event of
compressor failure or no air-conditioning option.
ZERO REHEAT ON - Supply air temperature is limited to the return air temperature.
Check Status Enable Operation Startup
Dectron, Inc. March 2012
Owners Manual
DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Data subject to change without notice.
231
STATUS MESSAGES
SCROLL DOWN
TO VIEW
Press
repeatedly to view any of the following Status messages that apply at the moment.
NOTE: In the list below the letter “X” is a placeholder for a number referring to a particular refrigeration circuit. On
your screen the appropriate number will appear rather than the “X”.
STARTUP
6.25

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DSV 040 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DSV 040 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DSV 040
CategoryController
LanguageEnglish

Related product manuals