DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owners Manual
Building Construction Heating and Cooling Availability
Data subject to change without notice.
24
DECTRON
Heating Availability
Room-temperature control is an important part of humidity control.
The dehumidifier capacity is matched to the rated pool-evaporation rate. The pool-evaporation rate will increase if
1. the pool temperature remains the same while room temperature is decreased, or
2. the pool temperature is increased while the room temperature remains the same.
Space heat must
be under the control of the DRY-O-TRON®. All installations must have space heat
available year-round. The DRY-O-TRON® will command only enough heat to keep the evaporation rate within a
workable range.
NOTE: Where space heaters are by others, the space heaters must heat the supply air. Do not install a heater in
the return duct.
NOTE: Unless equipped with a space heater, the DRY-O-TRON® does not produce significant heat - it
recycles heat. A dedicated space heater must be ordered with the unit or provided by others.
NOTE: Building heat losses are calculated by others and consequently are sized by others. Dectron does not
select space-heater capacities.
NOTE: Attempting to heat the air with the pool will increase the evaporation rate.
NOTE: Unless otherwise noted, hot-water or hot-glycol space heaters supplied by Dectron require the water or
fluid temperature to be between 160°F (71°C) and 180°F (82°C) for full heating capacity.
Cooling Availability
Where the DRY-O-TRON® unit has the cooling option and any required cooling water or other fluid is
provided by others, it is essential
that the cooling water or fluid be available at any time the DRY-O-TRON®
may be operating.
Do not
turn off cooling water or fluid based on time-of-day, time-of-year, outdoor temperature, or other
considerations.
design evaporation rate
actual evaporation
rate of pool
Evaporation Rate
(lb/hr)
+5°F-5°F-10°F-15°F
Graph Assumes Constant
Pool-Water Temperature
Room Temp.
Minus
Design Room Temp.
Design
Room Temperature
BUILDING
CONSTRUCTION
2.8

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DSV 040 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DSV 040 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DSV 040
CategoryController
LanguageEnglish

Related product manuals