Dectron, Inc. March 2012
DSH/DSV/RSH/DBH/RBH Series Dehumidifier Owner’s Manual
Service Troubleshooting Alarms
Data subject to change without notice.
284
To get an explanation of an alarm, first get the alarm on
screen. Press Prg to get the explanation.
For a list of alarm messages, see Operation - Alarm
Messages.
DECTRON
Reset
If the message “MANUAL RESET REQUIRED” appears
among the unit status messages, follow the instructions
on screen to accomplish a manual reset.
NOTE: Only certain specific alarms require manual reset.
Other alarms are automatic reset when the
problem is corrected.
If the alarm button is illuminated,
press it to see the current alarm(s).
Press
↓↓
repeatedly to see all current
alarms.
ALARM MESSAGES
SCROLL DOWN
TO VIEW
--- ALARM ---
XXXXXXXX
--- ALARM ---
XXXXXXXX
Correct all problems described
in alarm messages above.
MANUAL REST
REQUIRED
ENTER TO RESET
PERFORMING
MANUAL RESET
ENTER TO CONFIRM
ESC TO CANCEL
Display returns.
If prompted for a password, enter 1793 for
units made before April 2005. For units
made after April 2005, enter 17 or 1793.
Press
↵↵
to initiate the
resetting process.
Note: Not all alarms require
manual reset.
Press
↵↵
to proceed with the
resetting process.
Press Esc to cancel the
resetting process.