Dectron, Inc. March 2012
Owners Manual
DSH/DSV/RSH/DBH/RBH Series Dehumidifier
Data subject to change without notice.
295
Alarms Troubleshooting Service
DECTRON
Sensor cable disconnected
Sensor cable broken or shorted
Defective sensor
Be sure the sensor cable is properly
connected to both the sensor and the controller.
Disconnect the cable from the controller and
check the resistance of the sensor and cable
combination. Compare to the chart at the end
of this section.
If the resistance is outside the allowable range,
disconnect the cable from the sensor and be
sure the resistance of the cable is above 1 mil-
lion ohms. Connect the ends of the cable wires
together and be sure the cable resistance is
less than 5 ohms. If either condition fails,
replace cable.
Compare the resistance of the sensor itself
to the sensor resistance chart. Replace sensor
if necessary.
Connect sensor and cable to controller.
POOL 1 OUT SENSOR
FAULT
or
POOL 2 OUT SENSOR
FAULT
The signal from the inlet
pool water temperature
sensor is out of range.
Inadequate pool water flow rate
Be sure the pool water flow rate is as
specified in this manual.
Pool water temperature too high
Be sure the pool water set point is as
specified.
Be sure the pool water heating solenoid
valve closes. Check the solenoid valve signal.
Replace the valve as necessary.
POOL 1 LEAVING
WATER TOO HOT
or
POOL 2 LEAVING
WATER TOO HOT
The temperature of the
water returning to the
pool has exceeded
120°F. The unit will shut
down.
POOL 1 LOW WATER
FAULT
or
POOL 2 LOW WATER
FAULT
The flow detection
pressure switch circuit is
open. Pool water heat-
ing is inhibited.
Inadequate pool water flow rate
Be sure the pumps are working.
Be sure the valves are in the correct
position.
Check and set water flow rate as discussed
in Startup - Adjustments.
Defective pool water pressure
switch.
Set as discussed in Startup - Adjustments.
If the switch cannot be adjusted, contact
Dectron for a replacement.
Pool water pressure switch is not
adjusted
Set as discussed in Startup - Adjustments.
ALARM POSSIBLE CAUSES CHECKS & CORRECTIONS
8.15

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dectron DRY-O-TRON Supervisaire DSV 040 and is the answer not in the manual?

Dectron DRY-O-TRON Supervisaire DSV 040 Specifications

General IconGeneral
BrandDectron
ModelDRY-O-TRON Supervisaire DSV 040
CategoryController
LanguageEnglish

Related product manuals