Standard Requirements Ducts Installation
DECTRON
The table below is only a guideline for standard sea-level supply airflows and external static pressure drops.
Refer to the submittal data or to the unit nameplate for actual requirements.
Model Size Supply-air ESP Supply blower
(CFM) I.W.C. (HP)
010 1000 0.5 1
1.0 1
015 1200 0.5 1
1.0 1
020 2000 0.5 1.5
1.0 1.5
030 3000 0.5 2
1.0 2
040 3800 0.5 3
1.0 3
050 4800 0.5 3
1.0 5
060 5500 0.5 5
1.0 5
080 6500 1.0 5
2.0 7.5
100 8200 1.0 7.5
2.0 10
120 11000 1.0 7.5
2.0 10
150 13500 1.0 10
2.0 15
160 15000 1.0 15
2.0 15
180 16000 1.0 15
2.0 15
200 19000 1.0 15
2.0 20
240 20000 1.0 20
2.0 20
280 25000 1.0 20
2.0 25
360 32000 1.0 25
2.0 30
480 40000 1.0 30
2.0 40
560 50000 1.0 40
2.0 50
800 65000 1.0 60
Guideline Only
Use submittal data
or nameplate data.