A
STOP DRYING TEMP
Z
START DRYING TEMP
E
Today
R
NB DAYS DRYING
T
Normal regulation (End of drying)
Y
Heating temperature setting (°C)
Example
A
STOP DRYING TEMP: 47 °C
Z
START DRYING TEMP: 20 °C
R
NB DAYS DRYING
T
Normal regulation (End of drying)
Y
Heating temperature setting (°C)
Every day at midnight (00:00): the set point (START
DRYING TEMP) is recalculated and the remaining number
of days (NB DAYS DRYING) is decremented.
n
ROOM S.INFL
Used to adjust the influence of the room sensor on the water
temperature for the circuit concerned.
Adjustment
Description
0
No influence (remote control fitted in a location with no
influence)
1
Slight influence
3
Average influence (recommended)
10
Room thermostat type operation
n
NIGHT
This parameter is displayed if at least one circuit does not
include a room sensor.
For circuits without a room sensor:
4 NIGHT :DEC. (Reduced): The reduced temperature is maintained
during reduced periods. The circuit pump operates constantly.
4 NIGHT :STOP (Stop): Heating is shut down during reduced
periods. When installation antifreeze is active, the reduced
temperature is maintained during reduced periods.
2
3
4
1
6
5
C002768-A
00:00 00:00 00:00
2
10 9 8 7 6 5 4 3 2 1
23
20
26
29
32
35
38
41
44
47
4
4
5
1
6
C002769-A
00:00 00:00 00:00
5. Commissioning
Diematic iSystem For C 330 / C 630 ECO
59
31082018 - 7600691-001-06