Code Faults Cause
of the
fault
Description Checking / solution
L32 DEF.OUTLET S.
PCU The boiler flow sensor has short-
circuited
Bad connection
4 Check the wiring between the PCU PCB and the
sensor
4 Check that the SU PCB is correctly in place
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
L33
DEF.OUTLET S.
PCU The boiler flow sensor is on an
open circuit
Bad connection
4 Check the wiring between the PCU PCB and the
sensor
4 Check that the SU PCB is correctly in place
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensor
4 Replace the sensor if necessary
L34
FAN FAILURE
PCU The fan is not running at the right
speed
Bad connection
4 Check the wiring between the PCU PCB and the
fan
Fan defective
4 Check for adequate draw on the chimney
connection
4 Replace the fan if need be
L35 BACK>BOIL FAIL
PCU Flow and return reversed Bad connection
4 Check that the sensor has been correctly fitted
Sensor fault
4 Check the Ohmic value of the sensors
4 Replace the sensor if necessary
Water circulation direction reversed
4 Check the circulation (direction, pump, valves)
L36 I-CURRENT FAIL
PCU The flame went out more than 5
times in 24 hours while the burner
was operating
No ionization current
4 Purge the gas supply to remove air
4 Check that the gas valve is fully opened
4 Checking the gas supply pressure
4 Check the operation and setting of the gas valve
unit
4 Check that the air inlet and flue gas discharge
flues are not blocked
4 Check that there is no recirculation of flue gases
L37 SU COM.FAIL
PCU Communication failure with the
SU PCB
Bad connection
4 Check whether the SU PCB has been correctly
fitted into the connector on the PCU PCB
4 Change the SU PCB
Diematic iSystem For C 330 / C 630 ECO 7. Troubleshooting
31082018 - 7600691-001-06
76