EasyManuals Logo

DeDietrich INNOVENS PRO MCA 160 Technical Information

DeDietrich INNOVENS PRO MCA 160
4 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
QM
1/4 IT2683-en
Technical Information
Wall-hung gas condensing boilers
INNOVENS PRO MCA 160
Product evolution
JS IT2683-en 10/04/2019
1. Purpose
MCA 160 boilers equipped with a DIEMATIC EVOLUTION or INICONTROL2 control panel, evolve:
- Evolution of the DIEMATIC Evolution HMI : the new display is blue : better readability and quick access
icons.
- The following electronic boards (PCB's) are evolving, to optimize the cascade operation and the
management of domestic hot water:
The SCB-10 PCB changes from version 0.5 to version 1.02.
The burner management PCB: CU-GH06 changes from software version 1.9 to 2.1 version.
- Improved the siphon: easier removing and reassembly.
2. Compatibilities
In case of electronic card replacement, the compatibility of the software versions of the cards must be
checked, as indicated in the table below.
PCBs
SCB-10a
v 0.5
7636070
SCB-10c
v 1.02
7718260
CU-GH06 v 1.9
7628632
OK -
CU-GH06 v 2.1
7718238
- OK
Note: in blue, reference in spare parts (see point 4 hereafter).
CAUTION: In a cascade, the version of each card must be compatible with all other cards in the
cascade (all SCB-10 cards must be at the same version, as well as all CU-GH06 cards must be at the
same version).
EN

Other manuals for DeDietrich INNOVENS PRO MCA 160

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the DeDietrich INNOVENS PRO MCA 160 and is the answer not in the manual?

DeDietrich INNOVENS PRO MCA 160 Specifications

General IconGeneral
CategoryBoiler
TypeCondensing
ModelINNOVENS PRO MCA 160
Power Output160 kW
Max working pressure6 bar
Max temperature90°C
Electrical supply230V / 50Hz
Protection ratingIPX4D
Fuel TypeNatural Gas
EfficiencyUp to 109%
NOx emissionsClass 6
Connection diameterDN 50