Questions and Answers

  • C
    cjonesSep 10, 2025
    What to do if my DeDietrich INNOVENS PRO MCA 160 displays 'Deviation in flow sensor 1 and flow sensor 2 detected'?
    • D
      davidnguyenSep 10, 2025
      If your DeDietrich Boiler shows 'Deviation in flow sensor 1 and flow sensor 2 detected', it indicates a flow temperature sensor deviation. Check the connection for bad connections and replace the sensor if it's faulty.
  • J
    John SalazarAug 25, 2025
    What to do if my DeDietrich Boiler shows 'Max Tflow'?
    • K
      Kevin BrownAug 25, 2025
      If your DeDietrich Boiler displays 'Max Tflow', it means the flow temperature sensor is above the normal range. Check the wiring and connectors for bad connections, ensure the sensor is correctly fitted, and consider replacing the sensor if faulty. Also, check for no flow or insufficient flow by examining the circulation (direction, pump, valves), water pressure, and cleanliness of the heat exchanger.
  • G
    Gregory Taylor DDSAug 25, 2025
    What to do if my DeDietrich Boiler displays 'Gas Pressure Switch'?
    • D
      Diane ReyesAug 26, 2025
      If your DeDietrich Boiler displays 'Gas Pressure Switch', it indicates that the gas pressure is too low. You should check the gas supply pressure, ensure the gas tap is properly open, and inspect the wiring. If these are not the issue, the gas valve may be faulty and need to be checked or replaced.
  • A
    Angela BrownSep 23, 2025
    What to do if my DeDietrich INNOVENS PRO MCA 160 Boiler displays 'Uncritic device lost'?
    • P
      paul35Sep 23, 2025
      If your DeDietrich Boiler displays 'Uncritic device lost', it means the SCB PCB was not found. Check the connection.
  • R
    rosshuffmanSep 12, 2025
    What to do if my DeDietrich INNOVENS PRO MCA 160 displays 'Periodically safety check ongoing'?
    • G
      gsteeleSep 12, 2025
      No action is required. The device restarts itself when the DeDietrich Boiler displays 'Periodically safety check ongoing'.
  • C
    Christina WilsonSep 15, 2025
    What to do if my DeDietrich INNOVENS PRO MCA 160 displays 'Conf Error'?
    • L
      Lee TurnerSep 15, 2025
      If your DeDietrich Boiler displays 'Conf Error', it indicates a configuration error or unknown configuration number. Reset the boiler.
  • T
    tranandreSep 4, 2025
    What to do if my DeDietrich INNOVENS PRO MCA 160 displays 'THeat Ex Closed'?
    • J
      Jason ClineSep 4, 2025
      If your DeDietrich Boiler displays 'THeat Ex Closed', it indicates that the heat exchanger temperature sensor is short-circuited. Check the wiring and connectors for bad connections, ensure the sensor is correctly fitted, and replace the sensor if it is faulty.
  • D
    Dylan MillerSep 5, 2025
    What to do if my DeDietrich INNOVENS PRO MCA 160 displays 'WaterPressureOpen'?
    • L
      Lisa SmithSep 5, 2025
      If your DeDietrich Boiler displays 'WaterPressureOpen', it indicates that the hydraulic pressure sensor is open. Check the wiring and connectors for bad connections, ensure the sensor is correctly fitted, and replace the sensor if it is faulty.
  • L
    Lynn ArellanoSep 23, 2025
    What to do if my DeDietrich INNOVENS PRO MCA 160 displays 'Dhw Temp GradLevel3'?
    • A
      Ashley MelendezSep 23, 2025
      If the DeDietrich Boiler displays 'Dhw Temp GradLevel3', check the flow.
  • K
    kayleebaldwinAug 30, 2025
    What to do if my DeDietrich INNOVENS PRO MCA 160 displays 'False flame detected before burner start'?
    • J
      Jennifer WestAug 30, 2025
      If your DeDietrich Boiler displays 'False flame detected before burner start', it indicates a false flame signal. The burner may remain very hot. Check the ionisation/ignition electrode, and if no flame should be present but O 2 Ionisation current is measured. If necessary, replace the faulty gas valve or ignition transformer.

DeDietrich INNOVENS PRO MCA 160 Specifications

General IconGeneral
CategoryBoiler
TypeCondensing
ModelINNOVENS PRO MCA 160
Power Output160 kW
Max working pressure6 bar
Max temperature90°C
Electrical supply230V / 50Hz
Protection ratingIPX4D
Fuel TypeNatural Gas
EfficiencyUp to 109%
NOx emissionsClass 6
Connection diameterDN 50