EasyManua.ls Logo

DeDietrich S3 - Page 10

DeDietrich S3
16 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
Control panel S3 23/01/06 - 300008905-001-A
The table below specifies the way in which the cables are to be
connected on the burner control box.
If the electrical characteristics of the burner exceed the following
values
- inrush current > 16 A or
- P > 450 W or
-I > 2 A cos
ϕ = 0.7
The burner controls must be relayed, e.g. with the relaying kit
(package BP 51, optional)
.
7-pin plugs for connecting to the control panel and burner
connectors.
Connector
terminal -No
Wire No From Connection to the burner control box
L1 7 Continuous phase from the safety thermostat Burner main supply
4
V/J Earth connection Earth connection
N6Neutral taken after On/Off Neutral terminal
T1/T2 5/4 Dry contact of the stage 1 boiler thermostat Insert in the control circuit of boiler stage 1
S3 8 Burner alarm indicator Alarm output (phase)
T6 1 Stage 2 boiler thermostat input Insert in the control circuit of burner stage 2
T7 3 Stage 2 “boiler off” thermostat output Connect only if the burner is of the modulating type
T8 2 Stage 2 “boiler on” thermostat output Insert in the control circuit of burner stage 2
M000150
1