EasyManua.ls Logo

Dell EMC PowerEdge R7425 - 12 Appendix A. Additional Specifications; PSU Specifications

Dell EMC PowerEdge R7425
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
12
Appendix A. Additional specications
The following sections contain information about additional system specications.
PSU specications
The PowerEdge R7425 system supports up to two AC or DC power supply units (PSUs).
Table 30. PSU specications
PSU Class Heat
dissipation
(maximum)
Frequency Voltage High line
200v240 V
Low line
100– 140 V
DC Current
495 W AC Platinum 1908 BTU/hr
50/60 Hz
100–240 V AC,
autoranging
495 W 495 W N/A 6.5 A–3 A
750 W AC Platinum 2891 BTU/hr 50/60 Hz 100–240 V AC,
autoranging
750 W 750 W N/A 10 A–5 A
750 W AC Titanium 2843 BTU/hr 50/60 Hz 200–240 V AC,
autoranging
750 W N/A N/A 5 A
750 W
Mixed
Mode
HVDC (for
China only)
Platinum 2891 BTU/hr 50/60 Hz 100–240 V AC,
autoranging
750 W 750 W N/A 10 A–5 A
N/A 2891 BTU/hr N/A 240 V DC,
autoranging
N/A N/A 750 W 4.5 A
1100 W AC Platinum 4100 BTU/hr 50/60 Hz 100–240 V AC,
autoranging
1100 W 1050 W N/A 12 A–6.5 A
1100 W DC N/A 4416 BTU/hr N/A –(48–60) V DC,
autoranging
N/A N/A 1100 W 32 A
1100 W
Mixed
Mode
HVDC (for
China and
Japan
only)
Platinum 4100 BTU/hr 50/60 Hz 100–240 V AC,
autoranging
1100 W 1050 W N/A 12 A–6.5 A
N/A 4100 BTU/hr N/A 200–380 V DC,
autoranging
N/A N/A 1100 W 6.4 A–3.2 A
1600 W AC Platinum 6000 BTU/hr 50/60 Hz 100–240 V AC,
autoranging
1600 W 800 W N/A
10 A
2000 W
AC
Platinum 7500 BTU/hr 50/60 Hz 100–240 V AC,
autoranging
2000 W 1000 W N/A
11.5 A
2400 W
AC
Platinum 9000 BTU/hr 50/60 Hz 100–240 V AC,
autoranging
2400 W 1400 W N/A
16 A
64