Table 35. PowerMax 2000: Power consumption for 2 PowerBricks
Component Number of C13 outlets required Maximum total power
consumption > 35°C (VA)
Zone A Zone B Zone A + Zone B
PowerBrick 2 DAE 4 1 1 649
DAE 3 1 1 681
Engine 2 + SPS 1 1 1737
PowerBrick 1 DAE 2 1 1 649
DAE 1 1 1 681
Engine 1 + SPS 1 1 1769
TOTALS 6 6 6166
PowerMax 2000 rear-facing PDU requirements
If using a rear-facing PDU within a third-party rack, refer to the diagram below to ensure that the minimum width (F) and depth (A) of the
rack and PDU combination are sufficient for the array.
J
Figure 22. PowerMax 2000: Minimum requirements for third-party racks with rear-facing PDUs
Key
Description Minimum distance (in / cm)
A Minimum depth of the rack. Total value of B+C+D in the diagram.
B Distance between front surface of the rack post and the NEMA rail.
C Distance between the NEMA rails. 24 / 61
D Distance between the rear NEMA rails to the exterior, rear surface of the rack. 14 / 35.6
E NEMA rail spacing. 19 / 48.3
F Minimum width of the rack. Total value of E+K+K in the diagram.
G Distance between the rear-facing surface of the PDU and the surface of the rack
post. This space must be large enough to house power cables and route customer
host cables.
6 / 15.3
H PDU width.
52 Third Party Racking Option for PowerMax 2000