Use Dell Storage Manager to edit the Storage Center settings and set the operation mode of the Storage Center to Maintenance
mode.
Steps
1 Shut down the storage controller using Dell Storage Manager.
2 Make sure that all cables plugged into the storage controller are labeled.
3 Disconnect the cables from the storage controller that was shut down.
4 Remove the storage controller from the chassis
CAUTION: To prevent a thermal shutdown of the storage system, the service bae must be installed within three minutes
of removing the storage controller.
5 Install the service bae into the empty slot in the chassis.
6 Verify that the battery LED on the storage controller is o. It might take a few seconds for the LED to turn o.
7 Remove the cover from the storage controller.
8 Lift up the handle from the battery backup unit. The battery slides away from the cage connector.
Figure 14. Remove the Battery Backup Unit
1
Battery backup unit 2 Battery cage
3 Cage battery connector
Install the Battery Backup Unit
Use this procedure to install the battery backup unit.
Steps
1 Place the battery backup unit over the battery cage in the storage controller.
2 Lower the handle until it is ush with the battery.
The battery slides into the cage connector.
24
Replacing Storage System Components