Table 34. Expanded operating temperature specifications (continued)
Expanded operating temperature Specifications
For temperatures between 35°C to 40°C, de-rate maximum allowable
temperature by 1°C per 175 m above 950 m (1°F per 319 ft).
1% of annual operating hours 5°C to 45°C at 5% to 90% RH with 29°C dew point.
NOTE: Outside the standard operating temperature (10°C to
35°C), the appliance can operate down to 5°C or up to 45°C
for a maximum of 1% of its annual operating hours.
For temperatures between 40°C and 45°C, de-rate maximum
allowable temperature by 1°C per 125 m above 950 m (1°F per 228
ft).
NOTE: When operating in the expanded temperature range, appliance performance may be impacted.
NOTE: When operating in the expanded temperature range, ambient temperature warnings may be reported in the System
Event Log.
Expanded operating temperature restrictions
Do not perform a cold startup below 5°C.
The operating temperature specified is for a maximum altitude of 3050 m (10,000 ft).
150 W/8 core, 165 W/12 core and higher wattage processor [Thermal Design Power (TDP)>165 W] are not supported.
Redundant power supply units are required.
Non-Dell EMC qualified peripheral cards and/or peripheral cards greater than 25 W are not supported.
Mid drive tray is not supported.
Rear storage devices or drives are not supported.
GPU is not supported.
Thermal restrictions
Following table lists the configuration required for efficient cooling.
Table 35. Thermal restrictions configuration
Supported
VxRail
Config
Number
of proc
Heatsink Processor/DIMM
blank
DIMM
blanks
Type of air
shroud
Fan
VxRail P
Series
appliance
1 One 1U standard heat sink
for CPU 125 W
Required Not
required
Standard Four standard
fans and one
blank to cover
two fan slots
One 2U standard heat sink
for CPU > 125 W
VxRail P
Series
appliance
2 Two 1U standard heat sink
for CPU 125 W
Not required Not
required
Standard Six standard
fans
Two 2U standard heat sink
for CPU > 125 W
VxRail S
Series
appliance
1 One 1U high performance
heat sink
Required Required Not required Six high
performance
fans
VxRail S
Series
appliance
2 Two 1U high performance
heat sink
Not required Required Not required Six high
performance
fans
28 Technical specifications