CHASSIS ENCLOSURE & VENTILATION REQUIREM ENTS
ENCLOSURE VENTILATION
If your enclosure has doors, they need to be of a type that allows at least 30% airow through the enclosure
(front and back).
ENCLOSURE MINIMUM CLEARANCE
Leave a 10.2 cm (4 in.) minimum clearance on all vented sides of the computer to permit the airow required for
proper venlaon.
ENCLOSURE DOOR AREA
The intake and exhaust door areas should be, at a minimum, the same size as the system intake and exhaust areas.
RECOMMENDED ENCLOSURE
Do not install your computer in an enclosure that does not allow airow. This restricts the airow and impacts
your computer’s performance, possibly causing it to overheat.
OPEN DESK MINIMUM CLEARANCE
If your computer is installed in a corner, on a desk, or under a desk, leave at least 5.1 cm (2 in.) clearance from the
back of the computer to the wall to permit the airow required for proper venlaon.
REGULATORY COMPLIANC E AND ENVIRONMENTAL
Product related conformity assessment and regulatory authorizaons including Product Safety, Electromagnec Compability (EMC), Ergonomics,
and Communicaon Devices relevant to this product may be viewed at www.dell.com/regulatory_compliance. The Regulatory Datasheet for this
product is located at hp://www.dell.com/regulatory_compliance.
Details of Dell's environmental stewardship program to conserve product energy consumpon, reduce or eliminate materials for disposal, prolong
product life span and provide eecve and convenient equipment recovery soluons may be viewed at www.dell.com/environment. Product
related conformity assessment, regulatory authorizaons, and informaon encompassing Environmental, Energy Consumpon, Noise Emissions,
Product Materials Informaon, Packaging, Baeries, and Recycling relevant to this product may be viewed by clicking the Design for Environment
link on the webpage.