Table 9. Relative humidity specifications
Relative humidity Specifications
Storage 5% to 95% RH with 33°C (91°F) maximum dew point. Atmosphere
must be non-condensing at all times.
Operating 10% to 80% relative humidity with 29°C (84.2°F) maximum dew
point.
Table 10. Maximum vibration specifications
Maximum vibration Specifications
Operating 0.26 G
rms
at 5 Hz to 350 Hz (all three axes).
Storage 1.88 G
rms
at 10 Hz to 500 Hz for 15 min (all six sides tested).
Table 11. Maximum shock specifications
Maximum shock Specifications
Operating Six consecutively executed shock pulses in the positive and negative x,
y, and z axes of 6 G for up to 11 ms.
Storage Six consecutively executed shock pulses in the positive and negative x,
y, and z axes (one pulse on each side of the system) of 71 G for up to
2 ms.
Table 12. Maximum altitude specifications
Maximum altitude Specifications
Operating
3048 m (10,000 ft)
Storage 12,000 m (39,370 ft)
Table 13. Operating temperature de-rating specifications
Operating temperature de-rating Specifications
Up to 35°C (95°F) Maximum temperature is reduced by 1°C/300 m (1°F/547 ft) above
950 m (3,117 ft).
35°C to 40°C (95°F to 104°F) Maximum temperature is reduced by 1°C/175 m (1°F/319 ft) above
950 m (3,117 ft).
40°C to 45°C (104°F to 113°F) Maximum temperature is reduced by 1°C/125 m (1°F/228 ft) above
950 m (3,117 ft).
Particulate and gaseous contamination specifications
The following table defines the limitations that help avoid any equipment damage or failure from particulate and gaseous
contamination. If the levels of particulate or gaseous pollution exceed the specified limitations and result in equipment damage
or failure, you may need to rectify the environmental conditions. Remediation of environmental conditions is the responsibility of
the customer.
Table 14. Particulate contamination specifications
Particulate contamination Specifications
Air filtration Data center air filtration as defined by ISO Class 8 per ISO 14644-1
with a 95% upper confidence limit.
NOTE: The ISO Class 8 condition applies to data center
environments only. This air filtration requirement does not apply
to IT equipment designed to be used outside a data center, in
environments such as an office or factory floor.
18 Product Overview