EasyManua.ls Logo

Delt VFD Series - Page 73

Delt VFD Series
81 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
73 of 81
In firmware 1.05 3 additional settings were introduced for Pr02-00.
Select 4-5-6 instead of 1-2-3 to avoid this problem.
The response with these settings is faster and with higher initial output voltage.
Pr00-211 Operation command not via terminals
- Select Pr03-500.
- Using AVI or ACI:0~10V:
Set Voltage Lowest Point to 1V (Pr03-57 or 03-63).
Set Proportional Lowest Point to 10% (Pr03-58 or 03-64).
- Using ACI:0~20mA:
Set ACI Lowest Point to 2mA (Pr03-57).
Set ACI Proportional Lowest Point to 10% (Pr03-58).
With these settings some margins around 0V and 0Hz are set. Please change the
values if needed.
In firmware 1.06 this problem is solved and selecting Pr02-00 settings 4~5~6 is not
needed anymore for solving this problem.
Q How to calculate and set the OPL level?
A In Pr06-47 the trigger level for Output Phase Loss is set as a percentage of drive rated
current =100%. If one the output phase cuirrents >Pr06-47*Rated current for Pr06-46
time, OPL fault is generated. Please see the example below.
VFD rated current: 10A
Pr06-47=10%
One of three phase current < 1A for >Pr06-46 time, OPL is generated.