Chapter 6 Control Modes of Operation
Relevant parameters:
P1 - 34
TACC Acceleration Time Address: 0144H, 0145H
Default: 200 Related Section: Section
6.3.3,
Applicable Control Mode: S
Unit: msec
Range: 1 ~ 65500
Data Size: 16-bit
Display Format: Decimal
Settings:
This parameter is used to determine the acceleration time to accelerate from 0 to
its rated motor speed. The functions of parameters P1-34, P1-35 and P1-36 are
each individual. When P1-36 is set to 0 (Disabled), the settings of P1-34, P1-35 are
still effective. It indicates that the parameters P1-34 and P1-35 will not become
disabled even when P1-36 is disabled.
Please note:
1. When the source of speed command is analog command, the maximum setting
value of P1-36 is set to 0, the acceleration and deceleration function will be
disabled.
2. When the source of speed command is analog command, the maximum setting
value of P1-34 is limited to 20000 automatically.