Chapter 4 Parameter Settings|DD Series
4-50
Door Open DC Brake Starting Frequency
Control mode
VF
VFPG SVC FOCPG
Factory setting: 0.00
Settings 0.00~120.00Hz
During the period AC motor drive decelerating to stop, this parameter sets the DC brake starting
frequency If Pr.04-24 is lower than Pr.01-09 (starting frequency), DC brake will regards lowest frequency
as starting frequency.