EasyManua.ls Logo

Delta AS16AP11T-A

Delta AS16AP11T-A
460 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
AS Series Operation Manual
9-70
_9
Instance
Attribute
Name
Access
Rule
Data Type Values Description
H’03 Product Code Get UINT H’4000 Product Code
H’04
Revision
Get
STRUCT --
Revision of this device: Major /
Minor
Major Revision USINT H’01 Major Revision Range: H’01–H’7F
Minor Revision USINT H’01 Minor Revision Range: H’01–H’FF
H’05 Status Get WORD H’00
Status, refer to the following *1
table
H’06 Serial Number Get UDINT H’abcd
The last 4 characters of the MAC
address, ab:cd
H’07 Product Name Get STRING “AS300T
The maximum length of a product
name is 32 characters.
*1 Status Description (H’05)
Bit (s) Name Description
0 Owned
Does the device has an owner connection?.
0: No
1: Yes
1 Reserved
0Always OFF
2 Configured
Is the device configured?
0: No
1: Yes
3 Reserved
0Always OFF
4-7 Extended Device Status
0: Self-testing
1: Firmware update
2: At least one faulted I/O connection
3: No I/O connections established
4: Non-volatile configuration error
5: Major fault
6: At least one I/O connection in run mode
7: At least one I/O connection established, all in idle

Table of Contents