AS Series Operation Manual
2-3
_2
2.1 General Specifications
Item
Specifications
Operating temperature
-20 to 60°C
Storage temperature
-40 to 80°C
Operating humidity
5–95%
No condensation
Storage humidity
5–95%
No condensation
Work environment
No corrosive gas exists.
Installation location
In a control box
Pollution degree
2
Ingress protection
(IP ratings)
IP20
EMC (electromagnetic
compatibility)
Refer to Chapter 7 for more information.
Vibration resistance
Tested with:
5 Hz
f
8.4 Hz, constant amplitude 3.5 mm;
8.4 Hz f 150 Hz, constant acceleration 1g
Duration of oscillation: 10 sweep cycles
per axis on each direction of the three mutually perpendicular axes
International Standard IEC 61131-2 & IEC 60068-2-6 (TEST Fc)
Shock resistance
Tested with:
Half-sine wave:
Strength of shock 15 g peak value, 11 ms duration;
Shock direction: The shocks in each in direction per axis, on three mutually
perpendicular axes (total of 18 shocks)
International Standard IEC 61131-2 & IEC 60068-2-27 (TEST Ea)
Safety
Conforms to IEC 61131-2, UL508
Ambient air
temperature-barometric
pressure-altitude
Operating: 1080 ~ 795hPa (-1000 ~ 2000 m)
Storage:1080 ~ 660hPa (-1000 ~ 3500 m)

Table of Contents