Chapter 4 Fault Codes and DescriptionsParallel Control Solutions
25
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
214
SPI Tx Error
(CdE1)
CRC error occurs during data transmission from the
drive to the fiber card
Action and Reset
Action Condition
CRC error occurs during data transmission from the drive to the fiber card
Action Time
Act immediately
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
The drive and fiber card reconnect normally
Record
Yes
Cause
Corrective Actions
Fiber card abnormal
1. Check if the fiber card is installed firmly.
2. If the issue persists, replace the fiber card, and contact Delta.