Chapter 4 Fault Codes and DescriptionsParallel Control Solutions
29
ID
Display on LCD Keypad
Fault Name
Fault Descriptions
218
PCOM Torque Error
(PSTq)
Abnormal torque distribution
Action and Reset
Action Condition
More than 50% difference in torque distribution between master and slave
Action Time
Act immediately
Fault Treatment Parameter
N/A
Reset Method
Manual reset
Reset Condition
Reset immediately
Record
Yes
Cause
Corrective Actions
More than 50% difference in
torque between master and slave
1. Check if the drive parameters meet the description in parallel control
manual.
2. Check if the drive wiring is correctly installed on the motor side.

Related product manuals