Conduit ttings need to be water tight with either NEMA 4, 4X, 6, or 6X rated, and insulated type
preferred.
Once conduit and ttings are installed, route wiring thru conduit and tting and allowing a 6 inch
strain relief loop within the wiring box compartment.
Potential AC voltage loss in AC wires is possible to determine for a given wire cross section and
wire length. Delta recommends you select a wire size and length to ensure a maximum voltage
loss between 1 - 2 %. Please note that the diagrams only o󰀨er approximate voltage loss and more
precise voltage loss should be calculated by a licensed electrician in accordance with local, state,
and National Electrical Code ANSI/NFPA 70 requirements.