41
Percentage of voltage loss with 208 V AC and 240 V AC service. The load used in the calculation
is the maximum continuous AC current of the inverter.
2.0%
1.6%
1.2%
0.8%
0.4%
0.0%
20 40 60 80 100 120 140
One way distance in feet
Percent of voltage loss
10
AWG
8
AWG
6
AWG
Figure30:E6-TL-USvoltagelossindierentwiresizesandlengths
Percentage of voltage loss with 208 Vac and 240 Vac service. The load used in the calculation is
the maximum continuous AC current of the inverter.
2.0%
1.6%
1.2%
0.8%
0.4%
0.0%
20 40 60 80 100 120 140
One way distance in feet
Percent of voltage loss
8
AWG
6
AWG
Figure31:E8-TL-USvoltagelossindierentwiresizesandlengths
10
AWG