Chapter 14 Fault Codes and DescriptionsCP2000 
 
14-31
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
50 
 
Emergency stop   
(EF1) 
When the contact of MIx=EF1 is ON, the output stops 
immediately  and  displays  EF1  on  the  keypad.  The 
motor is in free running. 
Action and Reset 
Action level  MIx=EF1 and the MI terminal is ON 
Action time  Immediately act 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition  Manual reset only after the external fault is cleared (terminal status is recovered) 
Record  Yes 
Cause  Corrective Actions 
When MIx=EF1 activates 
Verify if the system is back to normal condition, and then press “RESET” key to 
go back to the default. 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
51 
 
External base block 
(bb) 
When  the  contact  of  MIx=bb  is  ON,  the  output  stops 
immediately and displays bb on the keypad. The motor 
is in free running. 
Action and Reset 
Action level  MIx=bb and the MI terminal is ON 
Action time  Immediately act 
Fault treatment parameter  N/A 
Reset method  The display “bb” is automatically cleared after the fault is cleared. 
Reset condition  N/A 
Record  No 
Cause  Corrective Actions 
When MIx=bb activates 
Verify if the system is back to normal condition, and then press “RESET” key to 
go back to the default. 
 
ID*  Display on LCD Keypad  Fault Name  Fault Descriptions 
52 
 
Password is locked 
(Pcod) 
Entering the wrong password three consecutive times 
Action and Reset 
Action level  Entering the wrong password three consecutive times 
Action time  Immediately act 
Fault treatment parameter  N/A 
Reset method  Manual reset 
Reset condition  Power-off 
Record  Yes 
Cause  Corrective Actions 
Incorrect password input through 
Pr.00-07 
1.  Input the correct password after rebooting the motor drive. 
2.  If you forget the password, do the following steps: 
Step 1: Input 9999 and press ENTER. 
Step 2: Repeat step 1. Input 9999 and press ENTER.   
(You need to finish step 1 and step 2 within 10 seconds. If you don’t finish   
the two steps in 10 seconds, try again.) 
3.  The parameter settings return to the default when the “Input 9999” process 
is finished.