English-15 
Parameter  Explanation  Settings 
Factory 
Setting
Customer
Pr.84 
Time Duration of 4th 
Step Speed 
00 to 9999 sec  00   
Pr.85 
Time Duration of 5th 
Step Speed 
00 to 9999 sec  00   
Pr.86 
Time Duration of 6th 
Step Speed 
00 to 9999 sec  00   
Pr.87 
Time Duration of 7th 
Step Speed 
00 to 9999 sec  00   
Pr.88 
Communication 
Address 
01 to 254  01   
Pr.89 Transmission Speed 
00: 4800 bps 
01: 9600 bps 
02: 19200 bps 
03: 38400 bps 
01  
Pr.90 
Transmission Fault 
Treatment 
00: Warn and Continue Operating 
01: Warn and RAMP to Stop 
02: Warn and COAST to Stop 
03: Keep Operation without Warning 
03  
Pr.91  Time Out Detection 
0.0: Disable 
0.1 to 120.0 sec 
0.0  
Pr.92 
Communication 
Protocol 
00: MODBUS ASCII mode, <7,N,2>  
01: MODBUS ASCII mode, <7,E,1> 
02: MODBUS ASCII mode, <7,O,1> 
03: MODBUS RTU mode, <8,N,2> 
04: MODBUS RTU mode, <8,E,1> 
05: MODBUS RTU mode, <8,O,1> 
00  
Pr.93 
Accel 1 to Accel 2 
Frequency Transition 
0.01 to 400.0 
0.00: Disable 
0.00  
Pr.94 
Decel 1 to Decel 2 
Frequency Transition 
0.01 to 400.0 
0.00: Disable 
0.00  
Pr.95  Auto Energy Saving  
00: Disable auto energy saving  
01: Enable auto energy saving  
00  
Pr.96 
Counter Countdown 
Complete  
00 to 9999  00   
Pr.97 
Preset counter 
countdown  
00 to 9999  00   
Pr.98 
Total Time Count from 
Power On (Days) 
00 to 65535 days 
Read 
Only
 
Pr.99 
Total Time Count from 
Power On (Minutes) 
00 to 1440 minutes 
Read 
Only
 
Pr.100 Software Version  ##   
Pr.101 
Auto Adjustable 
Accel/Decel  
00: Linear Accel/Decel 
01: Auto Accel, Linear Decel 
02: Linear Accel, Auto Decel 
03: Auto Accel/Decel 
04: Linear Accel/Decel Stall Prevention 
during Deceleration 
00