Chapter 14 Fault Codes and DescriptionsC2000 Plus
195
short
(ATTv)
When using Explorer for ASR Auto Tune, the operated
process is too short for the drive to complete the
frequency bandwidth estimation.
Action condition
The set number of turns is less than the minimum operation turn
Action time
N/A
Fault treatment parameter
N/A
Reset method
Manual reset
Reset condition
Reset immediately
Record
Yes
The operation process is too short
for the drive to estimate
1. Increase torque command to increase the acceleration speed
2. Increase the operation travel