Chapter 11 Summary of Parameter SettingsC2000 Plus
11-13
Pr. Parameter Name Setting Range Default
01-30 Skip Frequency 2 (Upper Limit) 0.00–599.00 Hz 0.00
01-31 Skip Frequency 2 (Lower Limit) 0.00–599.00 Hz 0.00
01-32 Skip Frequency 3 (Upper Limit) 0.00–599.00 Hz 0.00
01-33 Skip Frequency 3 (Lower Limit) 0.00–599.00 Hz 0.00
01-34 Zero-Speed Mode
0: Output waiting
1: Zero-speed operation
2: Minimum frequency (Refer to Pr.01-07 and Pr.01-41)
0
01-35
Motor 2 Rated / Base
Frequency
0.00–599.00 Hz
60.00 /
50.00
01-36
Motor 2 Rated / Base Output
Voltage
230V models: 0.0–255.0 V
460V models: 0.0–510.0 V
575V models: 0.0–637.0 V
690V models: 0.0–765.0 V
200.0
400.0
600.0
660.0
01-37 Motor 2 Mid-Point Frequency 1 0.00–599.00 Hz 3.00
01-38 Motor 2 Mid-Point Voltage 1
230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–637.0 V
690V models: 0.0–720.0 V
11.0
22.0
0.0
0.0
01-39 Motor 2 Mid-Point Frequency 2 0.00–599.00 Hz 1.50
01-40 Motor 2 Mid-Point Voltage 2
230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–637.0 V
690V models: 0.0–720.0 V
5.0
10.0
0.0
0.0
01-41
Motor 2 Minimum Output
Frequency
0.00–599.00 Hz 0.50
01-42
Motor 2 Minimum Output
Voltage
230V models: 0.0–240.0 V
460V models: 0.0–480.0 V
575V models: 0.0–637.0 V
690V models: 0.0–720.0 V
1.0
2.0
0.0
0.0
01-43 V/F Curve Selection
0: V/F curve determined by Pr.01-00–01-08
1: V/F curve to the power of 1.5
2: V/F curve to the power of 2
3: 60 Hz, voltage saturation in 50 Hz
4: 72 Hz, voltage saturation in 60 Hz
5: 50 Hz, decrease gradually with cube
6: 50 Hz, decrease gradually with square
7: 60 Hz, decrease gradually with cube
8: 60 Hz, decrease gradually with square
9: 50 Hz, medium starting torque
10: 50 Hz, high starting torque
0