Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-05-8
05-40
Permanent Magnet Synchronous AC Motor / Reluctance Motor Ld
Default: 0.00 / 0.0
Settings 0.00–655.35 mH / 0.0–6553.5 mH
05-41
Permanent Magnet Synchronous AC Motor / Reluctance Motor Lq
Default: 0.00 / 0.0
Settings 0.00–655.35 mH / 0.0–6553.5 mH
05-42
PG Offset Angle for a Permanent Magnet Synchronous AC Motor /
Reluctance Motor
Default: 0.0
Settings 0.0–360.0°
When you set Pr.05-00 as 4, the drive detects the offset angle and writes it into Pr.05-42.
05-43
Ke Parameter of a Permanent Magnet Synchronous AC Motor /
Reluctance Motor
Default: 0
Settings 0–65535 V / krpm
Permanent magnet motor parameter Ke (V
phase, rms
/ krpm)
When Pr.05-00 = 5, parameter Ke is calculated according to the motor’s actual operation.
When Pr.05-00 = 13, parameter Ke is automatically calculated according to the motor power,
current and rotor speed.