Chapter 12 Descriptions of Parameter SettingsC2000 Plus
12.1-07-4
Following table is the recommended setting for re-start delay time of each model power. You must
set Pr.07-08 according to this table (the default of each model power is based on this table as
well).
kW 0.75 1.5 2.2 3.7 5.5 7.5 11.0 15.0 18.5 22.0
HP 1 2 3 5 7.5 10 15 20 25 30
Delay time (sec.) 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 1.1 1.2
kW 30.0 37.0 45.0 55.0 75.0 90.0 110.0 132.0 160.0 185.0
HP 40 50 60 75 100 125 150 175 215 250
Delay time (sec.) 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2.0 2.1 2.2
kW 200.0 220.0 250.0 280.0 315.0 355.0 400.0 450.0 500.0 560.0
HP 270 300 340 375 425 475 536 600 650 750
Delay time (sec.) 2.2 2.3 2.3 2.4 2.5 2.6 2.7 2.8 3.0 3.2