Chapter 13 Warning CodesC2000 Plus
3
C
(CE3)
RS-485 Modbus illegal data value
When the length of communication data is too long
Warning setting parameter
Reset method
“Warning” occurs when Pr.09-
02=0 and the motor drive keeps running. The drive
resets automatically when receiving the correct communication data value.
Incorrect communication
Check if the communication command is correct.
Malfunction caused by
interference
Verify the wiring and grounding of the communication circuit. It is recommended
to separate
the communication circuit from the main circuit, or wire in 90 degree
for effective anti-interference performance.
Different communication setting
Check if the setting for Pr.09-04 is the same as the setting for the upper unit.
Disconnection or bad connection
Check the cable and replace it if necessary.
Communication data
error (CK3)
Keypad communication data, illegal data value
(Keypad auto-detect this error and display it.)
When the length of communication data is too long
Warning setting parameter
Remove the keypad and then reconnect it to the motor drive.
Incorrect communication
Keypad and the motor drive don’t communicate properly. It is recommended to
remove the keypad and then reconnect it to the motor drive.
Malfunction caused by
interference
Verify the wiring and grounding of the communication circuit. It is recommended
to separate the communication circuit from the main circuit, or wire in 90 degree
for effective anti-interference performance.
Different communication setting
Check if the Baud rate = 19200 bps. Format = RTU8, N, 2.
Disconnection or bad connection
Check the cable and replace it if necessary.