Chapter 13 Warning CodesC2000 Plus
13-8
ID No. Display on LCD Keypad Warning Name Description
7
Save error 1
(SE1)
Keypad COPY error 1: Keypad copy time-out
Action and Reset
Action condition
SE1
warning occurs when the keypad does not transmit the COPY command
to the drive, and does not transmit any data to the drive again in 10 ms at the
time you copy the parameters to the drive.
Action time 10 ms
Warning setting parameter N/A
Reset method Manual reset
Reset condition Immediately reset
Record N/A
Cause Corrective Actions
Communication connection error
SE1:
The causes of error are mostly communication problems between the
keypad and control board. Potential causes include
communication signal
interference and the unacceptable communication command to the Slave.
Check if the error
occurs randomly, or only occurs when copying certain
parameters (the error displays on the upper right corner of the copy page). If you
cannot clear the error, please contact Delta.
Keypad error
Control board error