EasyManuals Logo

Delta VFD040C43A-21 User Manual

Delta VFD040C43A-21
1259 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #877 background imageLoading...
Page #877 background image
Chapter 13 Warning CodesC2000 Plus
13-76
ID No. Display on LCD Keypad Warning Name Description
85
EtherNet/IP over
(ECo1)
Ethernet/IP exceeds maximum communication value
Action and Reset
Action condition Hardware detection
Action time Immediately acts
Warning setting parameter N/A
Reset method Manual reset
Reset condition Immediately resets
Record N/A
Cause Corrective Actions
The Master communication value
is more than the allowable quantity
of the communication card
Reduce Master communication value
The upper unit is online without
communicating, and does not
break off the Modbus TCP link,
causes occupy connection
Revise program of upper unit, the communication should be break off when it is
not used for a long time
A new Modbus TCP connection is
built every time when the upper
unit is connected to the
communication card, which
caused occupy connection
Revise program of upper unit: use the same Modbus
TCP connection when
connected to the same communication card

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Delta VFD040C43A-21 and is the answer not in the manual?

Delta VFD040C43A-21 Specifications

General IconGeneral
BrandDelta
ModelVFD040C43A-21
CategoryDC Drives
LanguageEnglish

Related product manuals