Chapter 14 Fault Codes and DescriptionsC2000 Plus
The length of motor cable is too
long
Increase AC motor drive’s capacity
Install AC reactor(s) on the output side (U/V/W)
Hardware fault
The ocd occurs due to short circuit or ground fault at the output side of the drive.
Check for possible short circuits between terminals with the electric meter:
B1 corresponds to U, V, W; DC- corresponds to U, V, W;
V, W.
If short circuits occur, return to the factory for repair.
Check if the setting of stall
prevention is correct
Set the stall prevention to the proper value.