Chapter 14 Fault Codes and DescriptionsC2000 Plus
ID* Display on LCD Keypad Fault Name Fault Descriptions
18
IGBT temperature
detection failure
(tH1o)
IGBT hardware failure in temperature detection
Action and Reset
Action condition NTC broken or wiring failure
Action time
When the IGBT temperature is higher than the protection condition, a
time exceeds 100ms, the tH1o protection occurs.
Fault treatment parameter N/A
Reset method Manual reset
Reset condition Reset immediately
Record Yes
Cause Corrective Actions
Hardware failure
Wait for 10 minutes, and then cycle the power. Check if tH1o protection still
occurs. If yes, return to the factory for repair.